APPLICATION
The Foam-Water Sprinklers are used in the deluge
foam system to protect the risk where foam is
required to be applied from overhead sprinklers and is
to be followed with plain water in a standard sprinkler
pattern.
Foam-Water Sprinklers protect the loading and
unloading area in the event of a spill fire with low
expansion foam systems. These are useful in other
applications like Air Craft Hangers, Warehousing etc.
SPECIFICATION
Foam-Water Sprinklers are open and air aspirating
type. The pattern of coverage is similar to the
conventional sprinkler head. The Foam-Water Sprinkler
has standard orifice with K-factor of 42.
Foam-Water Sprinklers are designed to operate at a
minimum of 2.1 bar pressure and maximum of 4.2 bar.
The Foam-Water Sprinkler with K-42 will deliver about
61 LPM at 2.1 bar pressure. The standard coverage
per Foam-Water Sprinkler is 9.3sq.m. (100 sq.ft.)
SYSTEM DESIGN
The Approval of the Foam Sprinkler is based on
the requirements of NFPA 13 and NFPA 16.
Discharge pattern provided is indicative only
and it is not to be used for design perpose.
Spacing between the sprinkler should not exceed as
mentioned in NFPA 13 for extra hazard occupancies.